Introduction of dynamic bandwidth in IDC computer Room

2025-01-14 Update From: SLTechnology News&Howtos shulou NAV: SLTechnology News&Howtos > Servers >

Share

Shulou(Shulou.com)06/02 Report--

Beijing Changping computer Room-Microgrid cohesion data Center

Computer room area: computer room area 1750 square meters, office 1620 square meters

Distribution room: UPS room, battery room with a total area of 3795 square meters

Building structure: floor load-bearing 800kg/ square meters, UPS room and battery room bearing 1000kg/ square meters

Electrostatic floor: the aerial height of the ground is 600mm. The ground under the electrostatic floor is insulated by non-flammable B1 rubber and plastic insulation board with a thickness of 19mm to prevent the loss of cold air and the condensation of the lower layer.

Lighting load level: the power consumption of emergency lighting is the primary load, the lighting in the computer room is the secondary load (with oil guarantee), and the rest is the tertiary load.

Beijing Changping computer room-microgrid cohesion data center maximum power / voltage: 49.2Kw/91.9A suction side operating overvoltage 0.14MPa

Exhaust side working overpressure 2.60MPa

Outdoor unit: model NACD26 rated power / current air conditioner brand: Nanjing Jiatu

Single machine cooling capacity of the three major computer rooms: 101. 2kW sensible cooling capacity: ≥ 94kW

Amount of humidification: 9.0kg/h calorie: 18.0kW

1260W/6.0A airflow: 24500CMH (- m ³/ h)

Energy efficiency ratio: 3.0 (high energy efficiency air conditioning = low energy consumption air conditioning national standard level 3 energy efficiency)

Cooling mode: air-cooled constant temperature and humidity air conditioning is adopted in the computer room.

Air supply mode: lower air supply, upper air supply

Online mode: co-work (work independently, work together)

Number of indoor units: 24 outdoor units: 48

Beijing Changping computer Room-Microgrid cohesion data Center

High-voltage power supply: introduced by Changping Science and Technology Park from two-way 10KV of Shanxia Power Station.

Power supply: low-voltage distribution system adopts ~ 220amp 380V, three-phase four-wire system, plus PE line AC power system.

UPS: in the brand, 2 sets of 400KVA (1x 1) UPS system constitute 2N system, and each distribution head cabinet receives power from 2 sets of UPS system respectively.

Equipment rated current: 1000002500A rated voltage: AC400V

Service user

The IDC group is stationed in the computer room 24 hours a day, and the service response is no more than 2 minutes. The network group monitors the master in real time and responds to the emergency at any time.

Solid technology

Microgrid cohesion CVM master control system, distributed cloud data center system, intelligent DNS system, CDN acceleration, online ICP filing and other network technologies to meet your development needs!

Clear positioning

All the services of microgrid cohesion are carried out on a stable basis, business and services are separated, demand is more clearly defined, prices are more reasonable, and high-quality services lead the technical direction.

Wu Wenyue

Company address: 503, 5th floor, Lianchuang Building, Shangdi West Road, Haidian District, Beijing

Welcome to subscribe "Shulou Technology Information " to get latest news, interesting things and hot topics in the IT industry, and controls the hottest and latest Internet news, technology news and IT industry trends.

Views: 0

*The comments in the above article only represent the author's personal views and do not represent the views and positions of this website. If you have more insights, please feel free to contribute and share.

Share To

Servers

Wechat

© 2024 shulou.com SLNews company. All rights reserved.

12
Report